Spectrosys Alarm / control unit Flocontrol TS
Spectrosys Alarm / control unit Flocontrol TS
- Automatic Controller capable of supporting: – Single Gas Panels – Single Gas Panels with supporting purge – Twin Gas panels (different source and destination) – Dual gas panels (same source and destination with auto changeover facility) – Supports MP3 and SBE3 configurations
- Alarm and control unit for 5 external digital sensor inputs, 8 system analogue inputs and 6 system digital inputs
- User adjustable purge cycles and service mode set points
- Line capacity calculator for optimised line purging
- Exhaust failure switch fitted as standard
- User selectable ACV (pn. operated cylinder valve)
- Touchscreen Operation: All operation from ergonomically positioned Human Machine Interface
- Industrial PLC controls all inputs and outputs as well as analogue signal processing
- 2 potential free outputs (one each for warning or shutdown conditions)
- Communication options: Ethernet, Profibus, Modbus RT and DeviceNet communications
- Solenoid valves can be manually operated by user
- An external junction box is supplied in order to allow fast connection of external sensors (e.g. gas detection) to the Flocontrol TS via a supplied 3 metre pre-plugged lead.
- Optional Heating Control System Add-on box for cylinder jackets and panel heating
- Digital inputs to be configured for NO or NC contacts
- Plastic housing IP 65 for wall mounting
- According to EC Directive 2004/108/EC (immunity and emission standard, measurement, control and laboratory use)
- According to Low Voltage Directive 2006/95/EC
- ATEX Equipment Directive 94/9/EC (Category 3 compliant where stated on the rating plate)
| Housing | |
| Protection Class : | IP 65 |
| Dimensions (WXHXD) | 300 x 200 x 1800 mm |
| Depending on Cabiner | 800 x 220 x 200 |
| Analogue Inputs | |
| Max. Switchable Voltage (Open circuit) : | 24 V DC |
| Short Circuit Current : | 25 mA |
| Power Supply Voltage | |
| Fuse : | 100-240 V/50-60 Hz |
| Max. Power Consumption | 2A |
| Output/ Pneumatic Valves | |
| Max Pressure : | 7 Bar |
| Compatibility : | Innert gases |
| NAMUR-Specification | |
| Voltage : | 5 V DC – 25 V DC |
| Power Input Inactive : | IL < 1 mA |
| Power Input Activated : | 3 mA < IL < 15 |
| Digital Inputs | |
| Power Supply Voltage : | 24 V DC |
| Max. Power : | 15 mA (per channel) |








