Spectrosys Alarm / control unit Flopurge TS
Spectrosys Alarm / control unit Flopurge TS
- Automatic purge controller
- Alarm and control unit for max. 10 digital inputs (e.g. contact pressure gauge or pressure switch), 8 analogue inputs (e.g. pressure transmitters) and one additional input for emergency shut off
- The unit may be used for 1 purge system including 3 pneumatic valves and 1 more individually programmable pneumatic valve
- User adjustable vent timer, pressurisation timer and purge cycles
- User selectable ACV (pn. operated cylinder valve) option or Extra Downstream EMO option
- Touchscreen Operation: All operation from ergonomically positioned Human Machine Interface
- Industrial PLC controls all inputs and outputs as well as analogue signal processing
- 4 potential free outputs (one for each valve status)
- Communication options: Ethernet, Profibus, Modbus RT and DeviceNet communications
- Solenoid valves can be manually operated by user
- Daylight visible LED indicators
- Acoustic signals can be silenced
- Digital inputs to be configured for NO or NC contacts
- Plastic housing IP 65 for wall mounting
- Password protection for 2 superior levels of access
- Multiple Language Support: supports up to four languages as standard
- According to EC Directive 2004/108/EC (immunity and emission standard, measurement, control and laboratory use)
- According to Low Voltage Directive 2006/95/EC
Housing | |
Protection Class : | IP 65 |
Dimensions (WXHXD) | 300 x 200 x 1800 mm |
Analogue Inputs | |
Max. Switchable Voltage (Open circuit) : | 24 V DC |
Short Circuit Current : | 25 mA |
Power Supply Voltage | |
Fuse : | 100-240 V/50-60 Hz |
Max. Power Consumption | 2A |
Output/ Pneumatic Valves | |
Max Pressure : | 7 Bar |
Compatibility : | Innert gases |
NAMUR-Specification | |
Voltage : | 5 V DC – 25 V DC |
Power Input Inactive : | IL < 1 mA |
Power Input Activated : | 3 mA < IL < 15 |
Digital Inputs | |
Power Supply Voltage : | 24 V DC |
Max. Power : | 15 mA (per channel) |